Seattle Fire Watch Closeout: 6 Steps From Red Tag to White Tag
Short answer: In Seattle, an SFD-certified technician must test the repaired system and replace the red impairment tag with a white tag. Only then does the owner cancel the fire watch, and the formal report goes to SFD within seven days.
1. Notify SFD if it will be down eight hours or more
The owner or impairment coordinator notifies the Seattle Fire Department when a system is expected to be out of service for eight hours or more.
2. Keep the fire watch running until restoration
The watch continues, with 15-minute patrols and an on-site log, for the whole impairment. Do not stop it when the repair crew leaves.
3. Have a certified technician test the system
After repairs, an SFD-certified technician tests the system.
4. Swap the red tag for a white tag
The technician removes the red impairment tag and places a white tag.
5. Tell everyone protection is restored
Notify the people you told about the impairment: building management, tenants, the alarm monitoring company, the repair company, and your insurance carrier.
6. Cancel the watch and file the report
The owner cancels the fire watch only after the system is restored. The formal report goes to SFD within seven days. Keep the fire watch log with your records.
Sources: Seattle Fire Department, CAM 5991: Fire Watch 路 Seattle Fire Department, Administrative Rule 9.04
More guides: Which Seattle Buildings Need a Dedicated Fire Watcher? 4 Occupancy Groups