Which Seattle Buildings Need a Dedicated Fire Watcher? 4 Occupancy Groups
Short answer: Under SFD Client Assistance Memo 5991, four occupancy groups need a dedicated fire watcher with no other duties, day and night, while a fire alarm or sprinkler system is impaired. Other buildings need a fire watch whenever they are occupied.
1. Assembly occupancies over 50 people
Restaurants, bars, event spaces, churches, and other assembly uses with a posted occupant load over 50 need a dedicated watcher at all times.
2. Hotels and apartments (R-1, R-2, R-3)
Hotels, apartments, and other residential occupancies need a dedicated watcher day and night. Patrols cover common areas, not private units.
3. Institutional occupancies
Hospitals, nursing homes, and similar facilities need a dedicated watcher day and night.
4. Schools and day cares (E)
Educational occupancies, including day cares, need a dedicated watcher day and night.
Everyone else: watch whenever occupied
Offices, stores, factories, warehouses, hazardous, and utility buildings need a fire watch whenever the building is occupied. Occupants doing their regular duties, including construction workers, can serve if they are told about the impairment and their duty to call 9-1-1.
Patrol every 15 minutes
In every case, each applicable area must be checked at least once every 15 minutes, and a fire watch log stays on site for SFD. A security company is not required; the owner chooses trained people who are available.
Sources: Seattle Fire Department, CAM 5991: Fire Watch 路 Seattle Fire Department, Administrative Rule 9.04
More guides: Seattle Fire Watch Closeout: 6 Steps From Red Tag to White Tag